Coil Guidlines

Diagram with Coil Specifications

Rows

  • Chilled Water and DX Coils 1 - 12
  • Hot Water Coils 1 - 12
  • Steam Coils 1 - 12
  • Condenser Coils 1 - 12
  • Booster Coils 1 - 12

FPI (Fins Per Inch)

  • 3/8" OD tube coils 10 - 20
  • 1/2" OD tube coils 6 - 16
  • 5/8" OD tube coils 6 - 14

Standard fins are .006" die formed aluminum with collared tube holes
Optional fins are .008" and .010" aluminum and .006" copper

Connection Sizes - Header Diameters

As shown in the chart, standard MPT and FPT connection diameters (OD's) range from 3/4" to 3". Contact factory for special connection sizes. For water coils, connection sizes are typically sized based on GPM of water.

Contact factory for fin coatings

DX Coils - Supply connections are brass distributors with removable type orifice and an optional side port connection for hot gas bypass